Baghdad Embassy Is Called A Fire Risk

Discussion Policy
Comments that include profanity or personal attacks or other inappropriate comments or material will be removed from the site. Additionally, entries that are unsigned or contain "signatures" by someone other than the actual author will be removed. Finally, we will take steps to block users who violate any of our posting standards, terms of use or privacy policies or any other policies governing this site. Please review the full rules governing commentaries and discussions. You are fully responsible for the content that you post.

Golden did not respond to e-mails, and French declined to comment. Miner did not respond to e-mails and phone calls. A spokesman for First Kuwaiti also declined to comment, citing restrictions under the company's contract. During construction of the project, the company has faced allegations of poor building and labor practices.

As early as October 2006, State Department fire inspectors raised concerns about the embassy's alarm and sprinkler systems. Several sources said the inspectors were denied permission to reinspect the systems after Golden and French assured them that the problems had been fixed.

Then, in September 2007, the pipes burst during a pressure test, and the inspectors discovered that many of the problems they had identified had been ignored. The inspectors documented hundreds of violations of the contract specifications and of fire codes and regulations, according to portions of the report made public by the House Oversight and Government Reform Committee in October.

Kennedy this week praised State's fire-safety experts as "pros, former fire marshals, who had identified problems out there so that they could be corrected."

One problem the inspectors raised was that First Kuwaiti had used plastic piping for the water mains. Although the firm's contract, dated May 13, 2005, called for plastic pipes, according to a copy, the State Department issued new regulations for embassies worldwide on Feb. 28, 2006, that insisted on cast-iron pipes. Ordinarily, such a change would be renegotiated with the contractor, but French did not tell First Kuwaiti of the change, according to two sources, and so it installed the wrong piping.

When the State Department inspectors identified this and other lapses in construction, Williams, the head of overseas building, hired another company, Schirmer Engineering of Chicago, to reinspect the fire-safety system. Schirmer produced reports on Oct. 22, Oct. 29 and Nov. 1 that uncovered even more problems. Williams and Golden appeared to minimize the issues in e-mails and directives, and then Schirmer's contract was ended. Williams did not respond to a request for comment, and Schirmer officials declined to comment.

First Kuwaiti then hired Hughes Associates, though it received an e-mail on Nov. 8 from a top State Department official saying that hiring such a consultant "is not a contract requirement." The Hughes representative signed a document stating that he witnessed a test of the fire-safety system on Dec. 7, but that did not mean he said it was working properly, said Philip J. DiNenno, president of Hughes.

"I am aware of some work done by the State Department inspectors and a contractor hired by State," DiNenno said, adding that Hughes is preparing a report on the fire systems. "I guess it wasn't coincidental that we heard from First Kuwaiti in November."

On Dec. 12, Williams initialed a statement saying that the underground piping for the fire system met requirements. On Dec. 28, project officials in Baghdad notified him that construction of the compound "has been substantially completed in accordance with the contract plans." Williams left the State Department three days later.


<       2